CCA and Cca look almost identical but describe completely different properties. CCA (upper case) is Copper-Clad Aluminium — a low-cost conductor material that does not comply with recognised Category cabling standards requiring copper conductors, and should be avoided. Cca (lower case "ca") is a Euroclass reaction-to-fire rating under the CPR. One is about the metal inside the cable; the other is about how it behaves in a fire.
Key Takeaways
- CCA (upper case) is Copper-Clad Aluminium — a low-cost conductor that does not comply with recognised Category cabling standards requiring copper conductors. Avoid it.
- Cca (lower case “ca”) is a Euroclass reaction-to-fire rating under the CPR.
- One is about the metal inside the cable; the other is about how the cable behaves in a fire.
- A cable can be genuine solid copper AND rated Cca — the two labels are unrelated.
- Read the datasheet: confirm “solid bare copper” and check the Euroclass separately.
On a datasheet they sit one letter's case apart, yet they describe completely unrelated things. Mix them up on a specification and you can end up ordering a completely different cable from the one the project requires.
CCA — Copper-Clad Aluminium (the conductor)
An aluminium core with a thin copper skin, used to cut cost. CCA can have roughly 55% greater DC resistance than solid copper cable of the same diameter, which increases heat and voltage drop under Power over Ethernet loads. It does not comply with the copper-conductor requirements of the Category cabling standards (Cat5e, Cat6, Cat6A), and professional installations avoid it. For the full detail, see our article on Solid Copper vs CCA Ethernet cable.
Cca — the Euroclass fire rating (how it behaves in a fire)
A reaction-to-fire classification under the EU Construction Products Regulation (CPR), classified in accordance with EN 13501-6. The scale runs Aca › B1ca › B2ca › Cca › Dca › Eca › Fca, from best to worst. Cca sits below B2ca and above Dca in the hierarchy. The Euroclass required for a given installation depends on national requirements, the building's fire strategy and the project specification — the CPR itself does not set Cca as a universal minimum for offices, schools or public buildings. See our Euroclass Fire Ratings article for the full ladder.
Why the mix-up is dangerous
A specification might call for "Cat6A Cca" — a fire class — and a supplier could ship "Cat6A CCA" — a cable using Copper-Clad Aluminium conductors. Those describe completely different properties — one is the conductor material, the other the fire class. The case of the letters and the context decide which is meant, so it pays to read carefully.
How to tell them apart at a glance
| Marking | Meaning | Where to look |
|---|---|---|
| CCA | Copper-Clad Aluminium conductor | Cable construction / conductor specification |
| Cca | CPR / Euroclass reaction-to-fire class | Fire performance / Declaration of Performance |
| Cca-s1b,d1,a1 | Cca plus smoke, flaming-droplet and acidity classifications | CPR / Euroclass declaration |
| Solid bare copper | Copper conductor construction | Cable datasheet |
- CCA appears in the conductor line of a datasheet: "bare copper" versus "CCA".
- Cca appears in the reaction-to-fire section of the datasheet or Declaration of Performance, often followed by additional smoke, flaming-droplet and acidity classifications, for example Cca-s1b,d1,a1.
- For permanent structured-cabling installations, check both properties separately: solid copper conductors and the required declared Euroclass — for example, a solid-copper Cat6A installation cable may have a declared Dca or Cca class; CCA refers to something entirely different.
The two properties are independent: a cable can be solid copper and Cca-rated at the same time. For an installation, specify solid copper together with the Euroclass required by the project.
Related Conversa products
For structured data cabling, Conversa specifies and supplies genuine solid copper rather than CCA, each with a stated Euroclass — and the fire class varies by cable:
- Excel Solid Cat6A S/FTP LSOH, Euroclass Dca-s2,d2,a2, 500m reel — Conversa SKU: 100-914 — solid copper with a declared Dca-s2,d2,a2 fire class.
- Excel Solid Cat6 U/UTP PE External Fca, 305m box — Conversa SKU: 100-100 — solid copper, external-grade, a different (Fca) fire class — showing conductor and fire class are separate.
Conversa can provide the manufacturer datasheet and CPR Declaration of Performance for the installation cables we supply, documenting both the conductor construction and declared Euroclass.
Related Conversa services
- Structured cabling design & installation — solid copper only, to the required Euroclass.
- Copper permanent-link testing & certification — field-tested with Fluke Networks equipment, with DC resistance and resistance-unbalance testing available where required to help identify non-compliant cabling such as CCA.
- Datasheet & CPR Declaration of Performance supply — proof of both conductor and fire class.
- Fibre-optic installation — where the design calls for it.
Frequently Asked Questions
What is the difference between CCA and Cca?
CCA (upper case) is Copper-Clad Aluminium, a low-cost conductor material to avoid. Cca (lower case "ca") is a Euroclass reaction-to-fire rating under the CPR. One describes the metal inside the cable; the other describes how the cable behaves in a fire. They are unrelated.
Is a "Cca" cable the same as a "CCA" cable?
No. They describe completely different properties. Cca is a reaction-to-fire classification; CCA describes the conductor construction. A cable can even be solid copper and Cca-rated at the same time.
Can a cable be both solid copper and Cca?
Yes. Solid copper describes the conductor, while Cca describes reaction-to-fire performance. Where Cca is the specified Euroclass, a cable can — and should — meet both requirements at the same time.
Why does the confusion matter?
A spec asking for "Cat6A Cca" (a fire class) could be mis-answered with "Cat6A CCA" (Copper-Clad Aluminium conductors). Reading the case or context wrong means ordering the opposite of what is required.
How do I check which one a datasheet means?
CCA appears in the conductor line ("bare copper" vs "CCA"); Cca appears in the reaction-to-fire section, often with additional smoke, flaming-droplet and acidity classifications such as Cca-s1b,d1,a1. Reputable manufacturers' datasheets clearly state the conductor construction and declared Euroclass.